    Example

    Assembly

    Two-row regulation station (RS) with measurement, which is designed for continuous operation.

    .

    Use

    Heating plants, brickyards, etc., where a 100 % backup at full capacity is required.

    Equipment

    In this case, the RS was designed for a flow rate of 1250 m3/h, which is provided by Tartarini regulators marked MBN. The safety of the regulation station against an increase in pressure on the outlet pipe from the regulator is ensured by the integrated slam shut valve OS/066 and the safety valve V/52. In the event of service or failure of the main series, the backup series takes over the function. In this case, the billing measurement is located on the middle pressure inlet pipe. The measuring series is designed with a measuring gallery.